Location of and Access to Laboratory |
Compliance with the following descriptions except when complying with Location of and Access to Laboratory in Attached Table 9-1 No.1 |
|
|
|
|
Animal experiment zone: separation (division) from general experiment zone |
Recommended |
Mandatory |
Mandatory |
Mandatory |
Establishment of shower facility near dressing room |
Recommended |
Recommended |
Recommended |
Recommended |
Establishment of general BL3 experiment zone, such as preparation of biological product |
- |
- |
Mandatory |
Mandatory |
Establishment of safe storage space for biological product |
- |
Mandatory |
Mandatory |
Mandatory |
Establishment of separate space for animal transport |
- |
Recommended |
Mandatory |
Mandatory |
Separation of animal breeding room and animal experiment space (surgery, dissection experiment, etc.) |
- |
Recommended |
Mandatory |
Mandatory |
Installation of storage facility or space for feed, litter, etc. in animal facility |
- |
Recommended |
Mandatory |
Mandatory |
Installation of exclusive washing and disinfection space for cage and apparatus and material related to animal breeding |
- |
Recommended |
Mandatory |
Mandatory |
Installation of pre-disposal animal carcass storage space and treatment facility in separate sealed zone in facility |
- |
Recommended |
Mandatory |
Mandatory |
Installation of equipment for pollutant removal and back draft prevention in case of installation of drainage |
- |
Recommended |
Mandatory |
Mandatory |
Experiment Zone |
Compliance with the following descriptions except when complying with Experiment Zone in Attached Table 9-1 No.1 |
|
|
|
|
Installation of observation window with insulated glass in animal breeding room |
- |
- |
Mandatory |
Mandatory |
Installation of window screen, flypaper sheet, etc. for preventing animals (including insects) from escaping |
- |
Recommended |
Mandatory |
Mandatory |
Air-conditioning |
Compliance with the following descriptions except when complying with Air-conditioning in Attached Table 9-1 No.1 |
|
|
|
|
Installation of separate airing duct |
- |
Recommended |
Mandatory |
Mandatory |
Installation of HEPA filter in air supply duct |
- |
Recommended |
Mandatory |
Mandatory |
Installation of carbon filter and other smell-removing equipment in exhaust system |
Recommended |
Recommended |
Mandatory |
Mandatory |
Maintenance of minimum negative pressure of 70Pa in animal room |
- |
- |
Mandatory |
Mandatory |
Experimenter Safety Protection |
Compliance with the following descriptions except when complying with Experimenter Safety Protection in Attached Table 9-1 No.1 |
|
|
|
|
Preparation of motor-type respiratory protective gear fitted with HEPA filter (except for suite-type Level 4 research facility) |
- |
- |
Mandatory |
Mandatory |
Experiment Apparatus |
Compliance with the following descriptions except when complying with Experiment Apparatus in Attached Table 9-1 No.1 |
|
|
|
|
Design of cage that has lid that is not easily opened by movement of animals, etc., is easy to clean and is made from material that allows disinfection and sterilization |
- |
Mandatory |
Mandatory |
Mandatory |
Establishment of facility or space, such as work cabinet with negative pressure function, for autopsy and replacement of cage, etc. |
- |
Recommended |
Mandatory |
Mandatory |
Waste Treatment |
Compliance with Waste Treatment in Attached Table 9-1 No.1 |
|
|
|
|
Other Facilities |
Compliance with Other Facilities in Attached Table 9-1 No.1 |
|
|
|
|
Installation of pre-filter in front end of exhaust filter in animal breeding and animal experiment space (except for space using sealed-type cage |
- |
Recommended |
Mandatory |
Mandatory |